208 - 240 VAC, NEMA L21-30P, Input Metered PDU
The ECX-MV1736060-G input-metered PDU distributes power to devices in the rack and offers real-time phase and circuit breaker metering and network monitoring of power loads for overload avoidance, capacity & load balancing, and energy use optimization. A hot-swappable network management controller allows for future upgrades andenhanced MTTR. The controller can also manage up to eight environmental sensors, or two security access handleswhich are managed through the PDU. The ECX-MV1736060-G can be managed by webUI, telnet or SSH, SNMP, or RESTful API.
Phase: 1PH
Acceptable Input Voltage: 208 - 240 VAC
Input Current: 30A (24A derated)
Input Plug: NEMA L21-30P
Outlet Configuration: Total: (36)C13, (6)C19, (2)5-15/20R: Per Breaker (12)C13, (2)C19,
with (2)5-15/20R on B1
Dimensions: 68.9” x 2.15” x 2.09” (1750 mm x 54.5 mm x 53 mm)
Dimensions (WxDxH) | 68.9” x 2.15” x 2.09” (1750 mm x 54.5 mm x 53 mm) |
---|---|
Orientation | Vertical |
Power Cord Length | 10' (3 m) |
Input Current | 30A (24A derated) |
Input Phase | 1PH |
Input Power | 8.6 kVA |
Overload Protection | (3) 20A, 2-pole, 10kAIC, hy-mag circuit breakers |
Outlet Configuration | Total: (36)C13, (6)C19, (2)5-15/20R: Per Breaker (12)C13, (2)C19, with (2)5-15/20R on B1 |
Safety Compliance | UL, CUL |
---|---|
EMC Compliance | CE-EMC, FCC, ICES |
Environmental Compliance | RoHS |