208 VAC; (12) C13 + (12) C19; CS8365C, Switched PDU

SKU
ECX-SV1812120-K
SKU: ECX-SV1812120-K

The ECX-SV1812120-K input metered, outlet switched PDU distributes power to devices in the rack and offers real-time phase and circuit breaker metering with network monitoring of power loads for overload avoidance, capacity & load balancing, and energy use optimization. Switched outlets allow power-up equipment sequencing, remote reboot, and outlet access control. A hot-swappable network management control allows for future upgrade and enhanced MTTR. Up to 8 optional environmental sensors and security access handles can be connected and managed through the PDU. ECX-SV1812120-K can be monitored through the embedded webUI, telnet, SNMP, or SSH interfaces.

Request Pricing

Phase: 3PH

Acceptable Input Voltage: 208 VAC

Input Current: 50A (3 phase)

Input Plug: Hubbell CS8365C

Outlet Configuration: Total: (12) C13 + (12) C19; Per Breaker: (2) C13 + (2) C19

Dimensions: 68.9" x 2.05" x 2.09" (1750 mm x 52 mm x 53 mm)

More Information
Dimensions (WxDxH) 68.9" x 2.05" x 2.09" (1750 mm x 52 mm x 53 mm)
Orientation Vertical
Depth at Circuit Breaker 2.95" (75 mm)
Power Cord Length 10' (3 m)
Input Current 50A (3 phase)
Input Phase 3PH
Input Power 27.7 kVA
Overload Protection (6) 20A, 2-pole, 10kAIC hy-mag circuit breakers
Outlet Configuration Total: (12) C13 + (12) C19; Per Breaker: (2) C13 + (2) C19
More Information
Circuit Breaker 10kAIC hy-mag circuit breakers
More Information
Safety Compliance UL, CUL
EMC Compliance CE-EMC, FCC, ICES
Environmental Compliance RoHS
For the most up to date information about the product you're interested in, please contact your sales representative.

Datasheet Download

User Manual Download

PDU Firmware Download