NAM, EMEA: 200-240/346-415VAC 3PH WYE, +6%, -10%,NAM, JP: 200-240VAC 3PH DELTA, 200-240VAC 1PH +6%, -10%, Total: (18)C13, Per breaker: (3)C13, Variable, Basic UPDU
The ECX-BH1818000-7 Basic UPDU offers a cost-effective option to users who do not require intelligence.
For greater flexibility the ECX-BH1818000-7 features a universal 7-pin input connector allowing
for interchangeable input power cables that can adapt to varying power sources depending on
the available facility power. Premium hydraulic-magnetic circuit breakers operate reliably in high
temperature environments. The Basic UPDU offers advanced features, such as color-coded IEC outlets
with support for W-lock cords and backed by a 5-year hassle free warranty.
Phase: 3PH
Acceptable Input Voltage:
NAM, EMEA: 200-240/346-415VAC 3PH WYE, +6%, -10%
NAM, JP: 200-240VAC 3PH DELTA, 200-240VAC 1PH +6%, -10%
Input Current:
EMEA 3PH: 32A
NAM 3PH: 30A (24A derated) 3PH, 50A (40A derated)
NAM 1PH: 30A (24A derated)
JP 3PH: 30A, 40A
JP 1PH: 30A
Input Plug: Variable
Outlet Configuration: Total: (18)C13, Per breaker: (3)C13
Dimensions: 3.43” x 17.44” x 7.76” (87 mm x 443 mm x 197 mm)
Dimensions (WxDxH) | 17.44” x 7.76” x 3.43” (443 mm x 197 mm x 87 mm) |
---|---|
Orientation | Horizontal |
Power Cord Length | Variable |
Input Current | EMEA 3PH: 32A NAM 3PH: 30A (24A derated) 3PH, 50A (40A derated) NAM 1PH: 30A (24A derated) JP 3PH: 30A, 40A JP 1PH: 30A |
Input Phase | NAM, EMEA: 200-240/346-415VAC 3PH WYE, +6%, -10% NAM, JP: 200-240VAC 3PH DELTA, 200-240VAC 1PH +6%, -10% |
Input Power | EMEA 3PH 400V: 22.0kVA (32A) NAM 3PH 208V: 8.6kVA (24A) or 14.4kVA (40A) NAM 3PH 415V: 17.3kVA (24A) NAM 1PH 208V: 5.0kVA (24A) JP 3PH 200V: 10.4kVA (30A) or 13.9kVA (40A) JP 1PH 200V: 6.0kVA (30A) |
Overload Protection | (6) 20A, 2-pole 10kAIC hy-mag circuit breakers |
Outlet Configuration | Total: (48)C13, Per breaker: (8)C13 |
Safety Compliance | UL, CUL |
---|---|
Environmental Compliance | RoHS |